免费观看女子推理社,韩国女主播一区二区,美女让我桶,欧美一级黄色片视频

當前位置:首頁-新聞中心新聞中心

變頻器通風管道的生活應用

發布人:http://www.bnlfans.net   發布時間:2018-02-24 17:10:06

高壓變頻器的發熱部件主要有兩部分:一是整流變壓器;二是功率元件,變頻器的冷卻方式-般采用空氣冷卻或者水冷卻。在動力功率較小時,采用自然空氣冷卻或空調冷卻滿足要求。在功率較大時,通過在散熱器中通水,利用循環水流帶走熱量。單純從散熱的角度,水冷是非常理想,即有冷卻效果又。但是,水循環系統工藝對密封要求很高,安裝復雜,維護量大,水循環系統一旦漏水,會帶來嚴重隱患。所以,能夠用空氣冷卻解決問題的場合,就不采用水冷。

The heating parts of high voltage frequency converter mainly consist of two parts: one is rectifier transformer, the other is the cooling way of power element and frequency converter -- air cooling or water cooling is adopted as the two. When power power is low, natural air cooling or air conditioning cooling can be used to meet the requirements. When the power is large, the heat is taken away by circulating water through the water in the radiator. Only from the angle of heat dissipation, water cooling is very ideal, that is, the cooling effect is energy saving and environmental protection. However, the water circulation system has a high requirement for sealing, complex installation and large maintenance. Once the water circulation system is leaking, it will bring serious security risks. Therefore, the air cooling can be used to solve the problem without water cooling.

變頻器冷卻的現狀及問題為了解決變頻器冷卻及防塵問題,南片水廠取水泵站配置4臺五匹吸頂式空調對變頻器發熱進行室內循環冷卻,在2017年6月開始的高峰供水期間,南片水廠取水泵站的兩臺高壓變頻器24h常態在45Hz運行。但是當氣象溫度在35℃以上時,安裝在室內的4套五匹空調全部開啟,卻還是無法將室溫降低變頻器允許的環境溫度40℃以下。變頻器發熱量近似值=變頻器容量X55W即1000kVAX0.9X55W=49.5kW;-匹空調制冷量近似值為2000kcal×1.162=2324W(其中,1.162為熱能能量轉換系數);五匹空調制冷量2324W×5匹=11.62kW,也就是說4臺五匹空調的制冷功率相當與-臺變頻器的發熱量。

The present situation and problems of inverter cooling cooling and converter dust in order to solve the problem, the south water pumping station equipped with 4 five pieces of ceiling type air conditioning indoor cooling of inverter in heating, the peak water supply during the beginning of June 2017, the south water pumping station two sets of 24h high voltage inverter in 45Hz normal operation. But when the meteorological temperature is above 35 C, the 4 sets of five air conditioners installed in the room are all open, but it is still unable to reduce the room temperature to the environment temperature below 40 C below the frequency converter. The inverter heat approximation converter capacity X55W = 1000kVAX0.9X55W=49.5kW; - horse air conditioners cooling capacity approximate value of 2000kcal * 1.162=2324W (among them, 1.162 for thermal energy conversion coefficient); five air-conditioning cooling capacity of 5 2324W * =11.62kW is horse, calorific value of refrigeration power of 4 sets of five air conditioning is equivalent to Taiwan converter.

20170427115450150.jpg

如果任由這種運行情況持續下去,將使變頻器出現故障的概率劇增,屆時不僅會產生高額的維修費用,還會導致取水泵站取水能力下降,進而影響南片水廠的高峰供水。南片水廠取水泵站從實際檢測數據顯示整流變壓器發熱大于功率單元元件的發熱量。如能把這部分的熱量引走,不僅可以降低室溫,還能減輕空調的負荷,減少空調的開啟臺數,實現降耗。

If this operation is allowed to continue, the probability of the failure of the inverter will increase sharply. At that time, it will not only generate high maintenance costs, but also cause the water intake capacity of the pumping station to decrease, and then affect the peak water supply of the south water plant. From the actual testing data of the pump station of the south water plant, the heating amount of the rectifier transformer is greater than that of the power unit element. If this part of the heat can be taken away, not only can reduce the room temperature, but also reduce the load of air conditioning, reduce the number of open air conditioning, to achieve energy saving and reducing consumption.

室內散熱問題的解決方法利用高壓變頻器自帶的軸流風機作為源動力,在整流變壓器柜體的軸流風機外邊加直徑為0.85m的通風管道到室外,整根通風管道不另行設置排風機,以實現變頻器熱量外循環,降低室內溫度,保護變頻器電子元件的目的。

The axial flow fan to solve the heat dissipation problem using the method of indoor high-voltage inverter comes as a source of power, the rectifier transformer cabinet axial fan outside diameter 0.85m ventilation pipe to the outside, the whole ventilation pipe without exhaust machine, in order to realize the inverter heat cycle, reduce the indoor temperature, the protection of electronic transducer the purpose of components.

安裝通風管道是解決變頻器散熱簡單而有效的方式,投入少見效快,高壓變頻器發熱量與外界自然空氣循環后,室內即不會產生空氣負壓,又降低室內環境溫度,由于空調少開、溫度降低后變頻器的效率提升等因素帶來的效益,初步測算,一年可以節省電費約4萬元。值得注意的是,直接與外界空氣循環后,需要增加變頻器的防塵設施空氣通過散熱通道時,空氣中的塵埃容易附著或堆積在變頻器內的電子元件上,從而影響散熱,嚴重時會縮短變頻器的壽命。

The installation of ventilation pipe is solved inverter simple and efficient way, less investment and quick, high voltage inverter heat and external natural air circulation, which does not produce indoor air negative pressure, and reduce the indoor temperature, less open, because the air conditioning temperature decreased after the inverter efficiency and other factors brought about energy efficiency, preliminary estimates, a year can save electricity about 40 thousand yuan. It is worth noting that, directly with the outside air circulation, the need to increase the frequency of air through the cooling channel of dustproof facilities, dust in the air easily attached or stacked electronic components in the frequency converter, thus affecting the heat, which will shorten the service life of the converter.


上一篇:黑白鐵皮加工有竅門!
下一篇:通風工程中的管道安裝要注意的細節知識

網站首頁 關于我們 產品展示 新聞中心 工程案例 在線留言 聯系我們

主站蜘蛛池模板: 又大又爽又湿又紧a视频| 亚洲欧美综合区自拍另类| 亚洲乱码一二三四五六区| 亚洲国产美女精品久久久久| 国产精品福利一区二区| 亚洲图片小说区| 老子影院午夜伦不卡| 韩国理伦大片三女教师| 国产美女免费观看| 午夜电影免费观看| 富二代国app产下载| 日韩1234| 老师开嫩苞在线观看| 欧美精品亚洲精品日韩专区| 99国产精品久久久久久久成人热| 干妞网在线观看| 天天看片天天射| 99视频在线免费看| 亚洲精品自拍视频| 欧美日韩三级在线观看| 琪琪色在线观看| 偷窥自拍10p| 午夜精品久久久久久久四虎| 美女脱了内裤打开腿让人桶网站o| 星空无限传媒在线观看| 国产高清免费在线| 免费人成在线观看视频播放| 99香蕉国产精品偷在线观看| 久久99久久99精品免观看| h在线观看网站| 欧美aaaaaaaa| 日本一卡2卡3卡4卡无卡免费 | 日韩福利影院| 成全高清视频免费观看| 色哟哟精品视频在线观看| 美女脱下裤子让男人捅| 香港一级毛片免费看| 欧美日韩国产另类一区二区三区| 亚洲人成7777影视在线观看| 伊人a.v在线| 粗大黑硬长爽猛欧美视频|